Quantity:


The detailed specifications for the Analog Input:

  • Input Type: Current (2, 3, or 4 wire devices)

  • Input Channels: Up to 32 per module

  • A/D Converter Resolution: 16 bit

  • Input Range: 0-20 mA or 4-20 mA

  • Normal Mode Rejection Ratio: 18 dB at 50 Hz, 20 dB at 60 Hz

  • Input Filter Response: Single pole, -3dB @ 6 Hz

  • Crosstalk (channel-to-channel): 60 dB (dc to 60 Hz)

  • Input Impedance: 250 Ω

  • Input Voltage Range: +33 VDC to -1 VDC

  • Input Scan Rate: 10 ms

  • Hardware Accuracy: 0.1% of full-scale (23.5 ± 2°C)

  • Short Circuit Current Limit: 25 mA for any 4 channels

  • Frequency Range: 0-15 kHz

  • Minimum Pulse Width: 25 µs

  • Output Type: 4-20 mA

  • Output Channels: Up to 32 per module

  • Output Temperature Drift: 0.007% of Full Scale/°C

  • Output Readback Diagnostic: ± 4% of Full Scale

  • Output Current Linearity: ± 0.05% of Full Scale (nominal)

  • Resolution: 12 bit

  • Calibrated Accuracy: < 0.35% of Full Scale (25oC) including linearity

  • Directly Settable Output Current Range: 0 mA, 2.9 mA to 21.1 mA

  • Maximum Resistive Load: 825 ohms @ 20 mA (with 24 V supply)

  • Maximum Output Compliant Voltage: 16.5 VDC @ 20 mA (with 24 V supply)

  • Open Circuit Voltage Supply: 26 VDC maximum

  • Response Time: 80 ms in HART mode, 0.25 ms in non-HART mode

  • Gap of Output to Field on Switchover: 0 ms (both partners continuously active)



Maybe you need the following products

Allen Bradley

ABB

Bently Nevada

Yokogawa

Emerson

Foxboro

GE Fanuc

Honeywell

Hima

ICS Triplex

Ovation

Prosoft

Siemens

Schneider

Triconex

Woodward


Part number

125740-01F2 DO 8 01  F2DO8 013BSE00469R1 PFBK164
125800-01F30033BSE018100R1 PM860K01
125840-01F3DIO16/8013BSE018103R1 CI853K01
125840-02F75533BSE018129R1/PM861
126599-01F8650ECI532V02 3BSE003827R1
126615-01F8650XCI532V03
128229-01K1412BCMA120 3DDE300400
128275-01K9203CMA121 3DDE300401


Previous: 
Next: